1 Introduction
Relay module 4-channel
Analog input module 4-channel
Analog input module 8-channel
Four relay outputs controlled via the system bus by digital sig-
nals
Each relay is equipped with a changeover contact
AC 230 V / 3 A
Separate terminal strip per relay output
Automatic configuration after the module insert has been ex-
changed during service work
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705015
Four universal analog inputs
Supported measuring probes: Thermocouples, RTD tempera-
ture probes, resistance transmitters, resistance/potentiome-
ters or standard signals (current or voltage)
The analog inputs are electrically isolated from each other
Customer-specific linearization possible by using a formula or
up to 45 pairs of values
Limit value monitoring
Automatic configuration after the module insert has been ex-
changed during service work
A digital input (DC 0/24 V) is also provided
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705020
Eight analog inputs for RTD temperature probes Pt100, Pt500
or Pt1000 in 2-wire circuit
The analog inputs are not electrically isolated from each other
Limit value monitoring
Automatic configuration after the module insert has been ex-
changed during service work
A digital input (DC 0/24 V) is also provided
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705021