43
6 Configuration
6.3 Digital input
In addition to the analog inputs the module provides a digital input.
The status of the digital input is indicated by a LED. The display corresponds to the output sig-
nal to the system bus.
Setup dialog
Parameter
Parameter Selection/settings Description
Mode: Delay 0 s to 65535 s Delay time during change of input signal
from Low to High (or from High to Low in
the case of active inverting)
Inverting Inversion of the input signal
Normal Not inverted
Inverse Inverted
TAG number 7 characters Identification marking (documentation in
PLC)
Signal suppres-
sion
Digital selector (Inactive)
Chapter 6.1 "Digital selector", page
33
Signal (high-active) for suppression of
the input signal
Level at suppres-
sion
Output level during active signal suppression
No choice Low level (0)
Active High level (1)
Alarm type The alarm type is not set by default.
CollectiveAlarm Alarm results in collective alarm of the
module.
Event Alarm results in an entry (event text) in
the event list.
Alarm active at High (1) Alarm at high level (1)
Low (0) Alarm at low level (0)