6 Configuration
38
Resistance Ra or Ro, Rs or Rx, Re
The overall resistance Ra + Rs + Re (or Ro + Rx) must not exceed 4000 Ω.
Status after change of configuration
The input values before the change of configuration are not saved; the new input values are
available approx. 2 seconds after the change of configuration.
Behavior after power on
All analog inputs are initialized and start their measurements over (no statuses are saved with
power off).
Resistance transmitter Resistance/potentiometer in 2-wire circuit
Resistance/potentiometer in 3-wire circuit Resistance/potentiometer in 4-wire circuit
Re
Rs
Ra
E
S
A
Rx
Ro
Ro
Rx
Ro
Rx